WIKA operating instructions process transmitter, model UPT-2x
14068347.01 06/2014 GB/D
GB
9.Congurationviadisplayandoperatingunit
4. Select “Mounting corr.” and conrm with [↵].
5. Select “change” and conrm with [↵].
6. Change digit using [▲] [▼] and conrm with [↵]. The
cursor moves to the next digit. Repeat for each digit.
Entered value will be used as the new zero point.
9.6 Settingthedamping
The damping prevents the uctuation of the output signal when there are short-term
uctuations in the measured value.
Pressure spikes will still be registered, e.g. as P
max
in the menu point
“Diagnostics”.
Setting range: 0 ... 99.9 s
1. Open the operating menu with [↵].
Select “Basic setting” and conrm with [↵].
2. Select “Damping value” and conrm with [↵].
3. Change digit using [▲] [▼] and conrm with [↵]. The
cursor moves to the next digit. Repeat for each digit.
Damping is set.