WIKA operating instructions air2guide model A2G-25
11
GB
40202755.02 07/2012 GB/D/F/E/I
5. Pressure output unit (and P OUT scale)
At 1,000 Pa At 2,000 Pa At 5,000 Pa At 7,000 Pa
0 ... 1,000 Pa 0 ... 2,000 Pa 0 ... 5,000 Pa 0 ... 7,000 Pa
0 ... 1 kPa
0 ... 2 kPa 0 ... 5 kPa 0 ... 7 kPa
0 ... 10 mbar
0 ... 20 mbar 0 ... 50 mbar 0 ... 70 mbar
0 ... 100 mmWS 0 ... 200 mmWS 0 ... 500 mmWS 0 ... 700 mmWS
0 ... 4 inchWS 0 ... 8 inchWS 0 ... 20 inchWS 0 ... 25 inchWS
The maximum value corresponds to an output signal of 10 V
6. Flow output unit for dening the V OUT
scale
7. V OUT scale, selectable:
m³/s → 10 V = 1 … 50 m³/s
m³/h → 10 V = 4,000 … 200,000 m³/h
cfm → 10 V = 2,000 … 100,000 cfm
l/s → 10 V = 1,000 … 50,000 l/s
scfh → 10 V = 1,000,000 … 6,000,000
scfh
lpm → 10 V = 60,000 … 3,000,000 lpm
8. Innite response time selection.
9. Press the END button and the instrument
returns to the display mode.
7. Zero point adjustment
Manual zero adjustment (standard)
1. Both the + and the – ow inputs must be disconnected
2. Press the zero point button until the red LED lights up
3. Wait until the LED switches o again. Now the instrument can be
reconnected.
4. In normal operation, we recommend that a zero adjustment is
carried out every 12 months.
6. Commissioning, operation / 7. Zero point adjustment