2266939.05 D/GB 06/2006
Universal IS Pressure Transmitter UniTrans
Transmitter Operation with HART®-functionality
Subject to change due to technical modifications. © Copyright WIKA Alexander Wiegand GmbH & Co. KG / Germany
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg · (09372) 132 - 710 · Fax - 706 · E-mail: sup[email protected] · www.wika.de
132
IUT-10 / IUT-11
4 mA ... 20 mA
250 W
Non-hazardous area
HART modem®
PC
+
-
051-DS-GB
If the resistances of the devices connected to the power supply/signal line (voltage
source) are less than 250
, a minimum resistance of 250 must be installed in the
power supply line. The sum of the internal capacitances and inductances of the com-
ponents used must not exceed the highest permissible values of the ia IIC circuit.
10.2 Operation via PC and the software PACT
ware
The PACTware software with the necessary device driver (DTM) can be ordered
from WIKA. An integration in other HART
®
management systems or FDT manage-
ment systems is possible.
Please note the different safety-related values according to the EC-type
examination certificate (see also chapter 6.7) and note the permissible
cable
length for devices with HART
®
communication.The termination resistor
in the loop must have a minimum value of 250
.
The necessary operating software
PACTware is described
in chapter 10.2.