8 Set up
8.1 Select the mode
The following modes can be adjusted on DPT10:
l Flow measurement
l Level measurement
l Dierential pressure measurement
8.2 Flow measurement
In ow measurement, normally DPT10 is used without isolating
diaphragm.
Before adjusting DPT10, you have to clean the eective pressure lines
and the instrument must be lled with the medium.
+
I
II
+
6
7
3
24
AB
Fig. 44: Preferred installation for gases
I DPT10
II 3-fold valve block
2.4 Inlet valves
3 Breather valve
6.7 Vent valves on DPT10
A, B Blocking valves
Instructions
Installation for gases
60 Dierential pressure transmitter DPT10 - metal measuring diaphragm Probus PA
8 Set up
37245-EN-100120