20 WIKA operating instructions level switch model LSD-30
GB
Parameter Description
SP1/SP2 Hysteresis function: Switch point switching output (1 or 2)
FH1/FH2 Window function: Window high switching output (1 or 2)
RP1/RP2 Hysteresis function: Reset point switching output (1 or 2)
FL1/FL2 Window function: Window low switch output (1 or 2)
EF Extended programming functions
RES Return the set parameter to the factory settings
DS1/DS2 Switch delay time, which must occur without interruption before any electrical signal change occurs
(SP1 or SP2)
DR1/DR2 Switch delay time, which must occur without interruption before any electrical signal change occurs
(RP1 or RP2)
OU1 Switching function switching output (1 or 2)
OU2 HNO = hysteresis function, normally open
HNC = hysteresis function, normally closed
FNO = window function, normally open
FNC = window function, normally closed
UNIT Changing units
SETR
Measuring range scaling (analogue output)
"4 mA" or "0 V" determines at which level the output signal is to be 4 mA or 0 V.
"20 mA" or "10 V" determines at which level the output signal is to be 20 mA or 10 V.
OFS Oset adjustment by 1,500 mm maximum (distance between start of measuring range and tank
bottom). Not possible with unit "%".
DISM Display value in display mode
ACT = actual level; LOW, HIGH = minimum, maximum level value OFF = display o;
SP1/FH1 = function switch point 1, RP1/FL1 = function reset point 1,
SP2/FH2 = function switch point 2, RP2/FL2 = function reset point 2,
DISR Rotate display indicator by 180°
RHL Clear the Min- and Max-value memories
PAS Password input, 0000 = no password, password input digit by digit
TAG Input of a 16-gure alphanumeric measuring point number
11613033.01 01/2012 GB/D/F/E
6. Commissioning, operation
6.4 Parameters