
21WIKA operating instructions level switch model LSD-30
GB
Display mode
▲ ▼
Long pressing of the "MENU" key
Programming mode
Factory setting:
▲ ▼
SP1 / FH1
Value
Min: MBA + 0.5 %, Max: MBE MBE
▲ ▼
RP1 / FL1
Value
Min: MBA, Max: SP1 -0.5 % MBE -10 %
▲ ▼
SP2 / FH2
Value
Min: MBA + 0.5 %, Max: MBE MBE
▲ ▼
RP2 / FL2
Value
Min: MBA, Max: SP2 -0.5 % MBE -10%
▲ ▼
EF RES
Yes / No
Reset to factory setting
▲ ▼
DS1
Value
0 ... 50 s 0 s
▲ ▼
DR1
Value
0 ... 50 s 0 s
▲ ▼
DS2
Value
0 ... 50 s 0 s
▲ ▼
DR2
Value
0 ... 50 s 0 s
▲ ▼
OU1
PARA
HNO, HNC, FNO, FNC HNO
▲ ▼
OU2
PARA
HNO, HNC, FNO, FNC HNO
▲ ▼
UNIT
Unit
mm, cm, inch, % order-related
▲ ▼
SETR
4 mA / 0 V Value
MBA + max. 25 % of span
MBA
▲ ▼
20 mA / 10 V Value
MBE - max. 25 % of span
MBE
OFS
Yes / No
Oset adjustment 1,500 mm maximum
0 mm
▲ ▼
ACT, HIGH, LOW, OFF, SP1/FH1, RP1/FL1,
SP2/FH2, RP2/FL2
ACTDISM
PARA
▲ ▼
DISR
Yes / No
Rotate display by 180°
▲ ▼
RHL
Yes / No
Reset HIGH, LOW
▲ ▼
PAS
Value
Password without
▲ ▼
TAG
Value
Measuring point number without
▲ ▼
Legend:
MBA = Start of measuring range
MBE = End of measuring range
END END
▼ ▼ ▼ ▼
Display mode
11613033.01 01/2012 GB/D/F/E
6. Commissioning, operation
Menu (programming and factory setting)
Comentarios a estos manuales