12 WIKA operating instructions OEM pressure transmitter, model OT-1
2127027.02 09/2013 GB/D/F/E
GB
6. Commissioning, operation / 7. Maintenance and cleaning
6.2.3 Setting up a voltage supply
The permissible power supply depends on the corresponding output signal.
Output signal Power supply U
+
Maximum load R
A
inΩ
4 ... 20 mA, 2-wire DC 8 ... 36 V R
A
≤ (power supply – 8 V) / 0.02 A
DC 1 ... 6 V, 3-wire DC 9 ... 36 V R
A
> 2.5 kΩ
DC 1 ... 5 V, 3-wire DC 8 ... 36 V R
A
> 2.5 kΩ
DC 0 ... 10 V, 3-wire DC 14 ... 36 V R
A
> 5 kΩ
DC 0.5 ... 4.5 V, ratiometric DC 5 ± 0.5 V R
A
> 4.5 kΩ
7. Maintenance and cleaning
7.1 Maintenance
This pressure transmitter is maintenance-free.
Repairs must only be carried out by the manufacturer.
7.2 Cleaning
CAUTION!
Before cleaning, correctly disconnect the pressure transmitter from the pressure supply, switch it o and
disconnect it from the power supply.
Electrical connections must not come into contact with moisture.
Wash or clean the dismounted instrument before returning it, in order to protect persons and the
environment from exposure to residual media.
Residual media in dismounted pressure transmitters can result in a risk to persons, the environment and
equipment. Take sucient precautionary measures.
Do not use any pointed or hard objects for cleaning, as they may damage the diaphragm of the process
connection.
For information on returning the instrument see chapter 9.2 “Return”.