Basic adjustment
Display
Diagnostics
Service
Info
2 Conrm the menu "Basic adjustment" with [OK], the menu item
"Unit" will be displayed.
Unit
Unit of measurement
bar
Temperature unit
°C
3 Activate the selection with [OK] and select "Units of measure-
ment with [->].
4 Activate the selection with [OK] and select the requested unit with
[->] (in the example mbar).
5 Conrm with [OK] and move to position correction with [->].
The adjustment unit is thus switched over from bar to mbar.
Information:
When switching over to adjustment in a height unit (in the example
from bar to m), the density also has to be entered.
Proceed as follows:
1 Push the [OK] button in the measured value display, the menu
overview is displayed.
2 Conrm the menu "Basic adjustment" with [OK], the menu item
"Units of measurement" will be displayed.
3 Activate the selection with [OK] and select the requested unit with
[->] (in the example m).
4 Conrm with [OK], the submenu "Density unit" appears.
Unit of measurement
Density unit
kg/dm³
pcf
5 Select the requested unit, e.g. kg/dm³ with [->] and conrm with
[OK], the submenu " D ensity" appears.
Unit of measurement
Density
0001000
kg/dm³
6 Enter the requested density value with [->] and [+], conrm with
[OK] and move to position correction with [->].
22 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor 4 20 mA
6 Set up with the indicating and adjustment module
37300-EN-100302