7
GB
WIKA Safety manual pressure transmitter, model S-20
14082128.02 06/2014 GB/D/F/E
2.3 Pin assignment
The assignment of the connection pins to the signals, and also the scaling of the signals, can be found on the product
label.
■
Connection 0 V / U-: Common terminal for negative operating voltage and signal ground.
■
Connection U+: Positive operating voltage
■
Connection S+: Signal output for voltage outputs
WARNING!
For instruments with plug-in electrical connections, the suitable connector must be used. The ingress of
moisture must be reliably prevented. The notes on commissioning in the operating instructions must be
observed.
2.4 Output signal/current parameters
Parameter Output signal
4 ... 20 mA
(2-wire)
20 … 4 mA
(2-wire)
DC 1 … 5 V DC 1 … 6 V DC 0.5 … 4.5 V DC 0.5 … 4.5 V
ratiometric
Span range 16 mA 16 mA 4 V 5 V 4 V 4 V * U
B
/ 5 V
Control range lower limit
value
3.6 mA 23 mA -0.4 V -0.4 V -0.4 V 0.1 * U
B
/ 5 V
Span
Initial limit value
3.8 mA 20.5 mA 0.9 V 0.9 V 0.4 V 0.4 V * U
B
/ 5 V
Span
Initial nominal value
4 mA 20 mA 1 V 1 V 0.5 V 0.5 * U
B
/ 5 V
Span
Final nominal value
20 mA 4 mA 5 V 6V 4.5 V 4.5 * U
B
/ 5 V
Span
Final limit value
20.5 mA 3.8 mA 5.5 V 6.5 V 4.7 V 4.7 V * U
B
/ 5 V
Control range upper limit
value
23 mA 3.6 mA 11.5 V 11.5 V 11.5 V 4.9 * U
B
/ 5 V
Nominal operating voltage
U
B
[V DC]
24 24 24 24 24 5
2. Safety
Comentarios a estos manuales