10 WIKA operating instructions models TR31-3, TR31-K
Explanation of symbols
Before mounting and commissioning the instrument,
ensure you read the operating instructions!
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant
European directives.
3. Specications
Thermometerwithtransmitterandoutputsignal4...20mA
(model TR31-x-x-TT)
Temperature range without neck tube -50 ... +150 °C
(-58 ... +302 °F), with neck tube
-50 ... +250 °C (-58 ... +482 °F)
1) 2)
Measuring element
Pt1000
Connection method
2-wire
Tolerance value of the measuring
element
Class A
3)
(per IEC 60751)
Measuring deviation of the
transmitter
±0.25 K
(per IEC 60770)
Total measuring deviation in
accordance with IEC 60770
Measuring deviation of the measuring
element + the transmitter
Measuring span
minimum 20 K, maximum 300 K
Basic conguration Measuring range 0 ... 150 °C
(-32 ... +302 °F), other measuring
ranges are adjustable
Analogue output
4 ... 20 mA, 2-wire
Linearisation
Linear to temperature per IEC 60751
Linearisation error
±0.1 %
4)
Switch-on delay, electrical (time
before the rst measured value)
max. 4 s
Warming-up period
After approx. 4 minutes, the instrument
will function to the specications
(accuracy) given in the data sheet.