6.4 Setup procedure
In HART-Multidrop mode (several sensors on one input) the address
must be set before continuing with the parameter adjustment. You will
nd a detailed description in the operating instructions manual
"Indicating and adjustment module" or in the online help of PACTware
or DTM.
HART mode
Standard
Address 0
IPT-1* can be used for level as well as for process pressure
measurement. Default setting is level measurement. The mode can be
changed in the adjustment menu.
Depending on the application only the respective subchapter "Level or
process pressure measurement" is of importance. There, you nd the
individual adjustment steps.
Level measurement
Set up IPT-1* in the following sequence:
1 Selecting adjustment unit/density unit
2 Carry out position correction
3 Carrying out min. adjustment
4 Carrying out max. adjustment
In the menu item "Adjustment unit" you select the physical unit in which
the adjustment should be carried out, e.g. mbar, bar, psi
The position correction compensates the inuence of the mounting
position or static pressure on the measurement. It does not inuence
the adjustment values.
Information:
The steps 1, 3 and 4 are not necessary for instruments which are
already preset according to customer specications!
You can nd the data on the type label on the instrument or in the
menu items of the min./max. adjustment.
The indicating and adjustment module enables the adjustmetn without
lling or pressure. Thanks to this, you can carry out your settings
already in the factory without the instrument having to be installed.
The actual measured value is also displayed in the menu items for
min./max. adjustment.
In this menu item you select the adjustment unit as well as the unit for
the temperature indication in the display.
Address setting HART-
Multidrop
Level or process pres-
sure measurement
Parameter ad-
justment "Level
measurement"
Select unit
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor 4 20 mA/HART 25
6 Set up with the indicating a nd adjustment module
31543-EN-090130